Parameter
Min
Max
Unit
Default
ID
Description
P3.13.5.5
SP1 Sleep Boost
-99999.9 9
99999.9 9
P3.13.1.4
0
1793
P3.13.5.6
SP1 Sleep Boost Maximum Time
1
300
s
30
1795
P3.13.5.7
SP2 Sleep Frequency
0.00
320.00
Hz
0.00
1075
See P3.13.5.1.
P3.13.5.8
SP2 Sleep Delay
0
3000
s
0
1076
See P3.13.5.2.
P3.13.5.9
SP2 Wake-up Level
-214748. 36
214748. 36
Varies
0.0000
1077
See P3.13.5.3.
P3.13.5.10
SP2 Wake-up Mode
0
1
0
1020
0=Absolute Level
1=Relative Setpoint
P3.13.5.11
SP2 Sleep Boost
-99999.9 9
99999.9 9
P3.13.1.4
0
1794
See P3.13.5.5
P3.13.5.12
SP2 Sleep Boost Maximum Time
1
300
s
30
1796
See P3.13.5.6
Table 80: Feedback Supervision Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.6.1
Enable Feedback Supervision
0
1
0
735
0 = Disabled
1 = Enabled
P3.13.6.2
Upper Limit
-99999.9 9
99999.9 9
Varies
Varies
736
P3.13.6.3
Lower Limit
-99999.9 9
99999.9 9
Varies
Varies
758
P3.13.6.4
Delay
0
30000
s
0
737
P3.13.6.5
Response to PID Supervision
Fault
0
3
2
749
0 = No action
1 = Alarm
2 = Fault (Stop according to stop
mode)
3 = Fault (Stop by coasting)
Table 81: Pressure Loss Compensation Parameters
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.13.7.1
Enable Setpoint 1
0
1
0
1189
0 = Disabled
1 = Enabled
P3.13.7.2
Setpoint 1 Max Compensation
-99999.9 9
99999.9 9
Varies
Varies
1190
P3.13.7.3
Enable Setpoint 2
0
1
0
1191
See P3.13.7.1.
P3.13.7.4
Setpoint 2 Max Compensation
-99999.9 9
99999.9 9
Varies
Varies
1192
See P3.13.7.2.