EasyManua.ls Logo

Danfoss VACON 100 FLOW Series - Page 323

Danfoss VACON 100 FLOW Series
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ID1780: 18 (minutes)
ID1781: 0 (seconds)
12.4.5 Energy Counter
The energy counter counts the total quantity of energy that the drive gets from the supply network. The counter cannot be reset. To
read the value of the counter through fieldbus, use these ID numbers.
ID number
Counter value
ID 2291
Energy Counter
The value always has 4 digits. The format and the unit of the counter change to agree with the energy counter value.
Example
0.001 kWh
0.010 kWh
0.100 kWh
1.000 kWh
10.00 kWh
100.0 kWh
1.000 MWh
10.00 MWh
100.0 MWh
1.000 GWh
and so on
ID number
Counter value
ID 2303
Energy Counter Format
The energy counter format gives the position of the decimal point in the value of the Energy Counter.
40 = 4 digits, 0 fractional digits
41 = 4 digits, 1 fractional digit
42 = 4 digits, 2 fractional digits
43 = 4 digits, 3 fractional digits
Example
0.001 kWh (Format = 43)
100.0 kWh (Format = 41)
10.00 MWh (Format = 42)
ID number
Counter value
ID 2305
Energy Counter Unit
The energy counter unit gives the unit for the value of the Energy Counter.
0 = kWh
1 = MWh
2 = GWh
3 = TWh
4 = PWh
AB298035655957en-000201 / DPD01083 | 323Danfoss A/S © 2023.08
Fault Tracing
VACON® 100 FLOW
Application Guide

Table of Contents