⚫  If you install at Ta 50°C environment, use coper wires that have a voltage rating of 600V and are 
temperature resistance to 75°C or 90°C. 
⚫  If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600V 
and are temperature resistance to 90°C or above. 
⚫  For VFD1K1VP43SHTCA models: if you install at Ta 45°C above environment, use copper wires 
that have a voltage rating of 600V and are temperature resistance to 90°C or above. 
⚫  For VFD1K2VP43SHTCA models: if you install at Ta 35°C above environment, use copper wires 
that have a voltage rating of 600V and are temperature resistance to 90°C or above. 
⚫  To be UL installation resistance of 75°C, in accordacne with UL requirements and 
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire. 
Main Circuit Terminals 
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3