Chapter 3 Electrical WiringVP3000
90
Frame L
Figure 3-30
If you install at Ta 50°C environment, use coper wires that have a voltage rating of 600V and are
temperature resistance to 75°C or 90°C.
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600V
and are temperature resistance to 90°C or above.
To be UL installation resistance of 75°C, in accordacne with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
Model
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3
Terminal
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
Max. Wire
Gauge
Min. Wire
Gauge
Screw Spec.
and Torque
(±10%))
VFD530VP43SHTCA
150 mm
2
*4
(300 MCM*4)
70 mm
2
*4
(2/0 AWG*4)
M12
360 kg-cm
(312.5 lb-in.)
(35.28 Nm)
150 mm
2
*2
(300 AWG*2)
70 mm
2
*2
(2/0 AWG*2)
M12
360 kg-cm
(312.5 lb-in.)
(35.28 Nm)
VFD616VP43SHTCA
95 mm
2
*4
(3/0 AWG*4)
95 mm
2
*2
(3/0 AWG*2)
VFD683VP43SHTCA
120 mm
2
*4
(4/0 AWG*4)
120 mm
2
*2
(4/0 AWG*2)
VFD770VP43SHTCA
120 mm
2
*4
(250 MCM*4)
120 mm
2
*2
(250 MCM*2)
Table 3-24