Chapter 6 Drive Communication Network|VP3000
256
1: Enable function of bit6–11
Frequency command (xxx.xx Hz), two decimal points for standard
drives; one decimal point for high-speed drive.
Fault/
Control
command
source
Used to clear the fault status.
4. Status monitor read only (21xx)
AC Motor drive
status
(Low word)
AC motor drive operation status
00b: Drive stops (keypad RUN light OFF/ STOP light
ON)
01b: Drive stopping (keypad RUN light flashes / STOP
light ON)
10b: Drive standby (keypad RUN light ON / STOP light
flashes)
11b: Drive operating (keypad RUN light ON / STOP
light OFF)
NOTE: this bit is used to detect the drive operating
status, to control the LED display for the operation
status.
Operation Direction
00b: The drive is in FWD run status (Keypad REV light
OFF / FWD light ON)
01b: The drive runs from current REV direction to target
FWD direction (keypad REV light flashes / FWD
light ON)
10b: The drive runs from current FWD direction to
target REV direction (keypad REV light ON / FWD
light flashes)
11b: The drive is in REV direction (keypad REV light
ON / FWD light OFF)
NOTE: this bit is used to detect the drive operating
direction, to control the LED display for the running