Chapter 8 Troubleshooting|VP3000 
407 
 
Warning Setting Parameter 
H2-14 
0: Warning & continue OPER 
1: Fault & Ramp to Stop 
2: Fault & Auto-Decel 
3: Fault & coast to stop 
4: Fault & by Quick Stop Time 
“Warning”  occurs  when  Pr.  H2-14  =  0.  The  “Warning”  automatically 
clears when the output current is > (Pr. H2-12 × 105%). 
“Error” occurs when Pr. H2-14 = 1–4. You must reset manually. 
Does not record when Pr. H2-14 = 0 and uC displays “Warning” 
Motor cable disconnection 
Exclude the connection issue of the motor and its load. 
Improper setting for the low 
current protection 
Set the proper settings for Pr. H2-12, Pr. H2-13 and Pr. H2-14. 
Check the load status. 
Make sure the motor capacity matches the load.