Chapter 8 TroubleshootingVP3000
426
ID No.
Warning Name
Descriptions
32
Overload
(OLD)
The load is higher than the user defined loading curve and triggers overload
protection.
Action and Reset
Action Condition
The loading condition is higher than Pr. H7-05H7-14 loading curve
Action Time
Pr. H7-04
Warning Setting Parameter
H7-02
0: Warning & continue OPER
1: Fault & Ramp to Stop
2: Fault & Auto-Decel
3: Fault & coast to stop
4: Fault & by Quick Stop Time
Reset Method
The warning is automatically cleared when the load is lower than the setting
loading curve.
Reset Condition
The warning is automatically cleared when the load is lower than the setting
loading curve.
Record
Yes
Cause
Corrective Actions
Incorrect settings that trigger the
protection
Check if the setting for H7-05H7-14 is correct.