Chapter 8 Troubleshooting|VP3000 
427 
 
Before the AC motor drive operates, it detects that the DC bus voltage is lower 
than Pr. H1-02 setting value 
DC bus voltage is lower than Pr. H1-02 setting value 
Immediately act when DC bus voltage is lower than Pr. H1-02 
Warning Setting Parameter 
It can be reset after the DC bus voltage exceeds the following voltage. 
460V models: Pr. H1-02 + 60 V
DC
 
Improve power supply condition. 
Adjust voltage to the power range of the drive. 
Start up the motor with large 
capacity 
Check the power system. 
Enlarge the capacity of power equipment. 
Reduce the load. 
Enlarge the drive capacity.