Chapter 8 TroubleshootingVP3000
437
ID No.
Warning Name
Descriptions
60
PLC scan time fail
(PLSF)
PLC scan time-out during program execution
Action and Reset
Action Condition
When the PLC scan time exceeds the maximum allowable time (200 ms), PLSF
warning shows.
Action Time
Immediately act when the error is detected
Warning Setting Parameter
N/A
Reset Method
Check if the program is correct and re-download the program. If the fault does
not exist after re-download the program, the warning automatically clears.
Reset Condition
No
Record
No
Cause
Corrective Actions
The PLC scan time exceeds the
maximum allowable time (200 ms)
Check if the PLC program uses excessive FOR and CALL commands, reduce
the usage and re-download the program.