Chapter 8 TroubleshootingVP3000
438
ID No.
Warning Name
Descriptions
70
ExCom ID fail
(ECid)
Duplicate MAC ID error
Node address setting error
Action and Reset
Action Condition
Duplicate setting of MAC ID
Node address setting error
Action Time
No
Warning Setting Parameter
N/A
Reset Method
Correct the setting and cycle the power
Reset Condition
No
Record
No
Cause
Corrective Actions
The setting address exceeds the
range (0–63)
Check the address setting of the communication card (Pr. n4-01, n4-06).
The speed setting exceeds the
range
Standard: 0–2, non-standard: 0–7
The address is duplicated with
other nodes on the BUS
Reset the address