Chapter 8 TroubleshootingVP3000
471
ID No.
Warning Name
Descriptions
153
Monitor signal 8 trigger
(BX8n)
Sets the monitor signal source o2-50 according to the trigger condition, and the
monitoring signal meets the trigger condition.
Action and Reset
Action Condition
Meet Pr. o2-51 trigger condition
Action Time
Immediately act
Warning Setting Parameter
Pr. o2-52
0: Disable
1: Warning
2: Fault and ramp stop
3: Fault and coast stop
Reset Method
Manual reset
Reset Condition
Does not meet Pr. o2-51 trigger condition
Record
Records when Pr. o2-52 = 2 or 3
Cause
Corrective Actions
Incorrect settings that trigger the
protection
Check if the setting for o2-50, o2-51 and o2-52 is correct.