Chapter 8 Troubleshooting|VP3000 
504 
 
Low voltage at constant 
speed (Lvn)   
DC bus voltage is lower than Pr. H1-02 setting value at constant speed 
Pr. H1-02 (Default = depending on the models)   
Immediately act when DC bus voltage is lower than Pr. H1-02 
Fault Treatment Parameter 
It can be reset after the DC bus voltage exceeds the following voltage. 
460V models: Pr. H1-02 + 60 V
DC
 
Improve power supply condition. 
Adjust voltage to the power range of the drive. 
Start up the motor with large 
capacity 
Check the power system. 
Enlarge the capacity of power equipment. 
Reduce the load. 
Enlarge the drive capacity.