Chapter 8 Troubleshooting|VP3000 
505 
 
Phase Loss Protection   
(OrP)   
Phase loss of power input 
The DC bus ripple is higher than the system allowed range 
Fault Treatment Parameter 
Pr. H3-00 (OrP Action) 
0: Warning & continue OPER 
1: Fault & Ramp to Stop 
2: Fault & Auto-Decel 
3: Fault & coast to stop 
4: Fault & by Quick Stop Time 
Automatically resets when Pr. H3-00 = 0 as “Warning” 
It is “Fault” when Pr. H3-00 = 1–4, which must be reset manually. 
Immediately resets when the DC bus ripple is within the system allowed range. 
Records when Pr. H3-00 = 1–4 and OrP displays “Fault” 
Phase loss of input power 
Correctly install the wiring of the main circuit power. 
Single phase power input to three-
phase model 
Choose the model whose power matches the voltage. 
If the main circuit power works normally, verify the main circuit. 
Cycle the power after checking the power, if OrP error still exists, return to the 
factory for repair. 
Loose wiring terminal of input 
power 
Tighten the terminal screws according to the torque described in the user manual. 
The input cable of three-phase 
power is cut off 
Wire correctly. 
Replace the cut off cable. 
Input power voltage changes too 
much 
Check if the input power voltage signal fluctuates. 
Unbalanced three-phase of input 
power 
Check the power three-phase status.