⚫ If you install at Ta 45°C environment, use coper wires that have a voltage rating of 600V and are
temperature resistance to 75°C or 90°C.
⚫ For VFD395VP43xxTCA models: if you install at Ta 45°C above environment, use copper wires that
have a voltage rating of 600V and are temperature resistance to 90°C or above.
⚫ To be UL installation resistance of 75°C, in accordacne with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3