Firmware V3.13
21.04.2021
199/466
Menu2-1-2Zone2
COOLING 2 POS: XXXXX Entry Default
Setpoint R2.2 XXX °C Supply air temperature
setpoint
--, -10..20
Hystersis R2.2 X K Supply air temperature
hysteresis setpoint;
shown only when on-off
control is set (Menu
2-1-2)
1..8
Setpoint R4.2 XXX °C Return air temperature
setpoint
--, -10..20
Hystersis R4.2 X K Return air temperature
hysteresis setpoint;
shown only when on-off
control is set (Menu
2-1-2)
1..8
Superheat XXX K Superheat setpoint Zone
2
0..20
Min. SH XX K Minimun superheat
setpoint, below which
cooling relay switches off
Zone2.I-sum(notI-part)
is set to zero when the
Reset I-Sum parameter is
set to ON.
0..10
Two pos.ctrl XXX Switch between on-off
control (ON) and
continuous control (OFF)
↑,↓(ON/OFF)
MOP-point XXX °C Starting setpoint for MOP
mode
--, -50..50
Cool. on AOUT XXX% Kühlung eingeschaltet:
fester Wert 0..10 V für
Analogausgang AO2; nur
sichtbar, wenn von DIP-
Schalter S3 der
Kodierschalter 6 auf ON
steht, siehe Kapitel
Funktionsweise der
Analogausgänge 0..10 V.
80 %
Cool. off AOUT XXX% Kühlung ausgeschaltet:
fester Wert 0..10 V für
Analogausgang AO2; nur
sichtbar, wenn von DIP-
Schalter S3 der
Kodierschalter 6 auf ON
steht, siehe Kapitel
Funktionsweise der
Analogausgänge 0..10 V.
50 %