• Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX Entry Default
Counting Rate X Setpoint of time during which evaporator defrost
terminiation temperature may be within band around
0°C before defrost counter counts down
0..15 3
Defrost Counter X Setpoint of count for number of defrost cycles to be
skipped. By pressing the ↵ key the value can be set to 1
until it is automatically reset to the basic settings.
6
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 10 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15
3 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 5 min
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function. For
details see chapter Master/slavemode–defrost
synchronisation via CAN bus.
OFF,
MASTR,
SLAVE
OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in the
defrost via CAN bus which is the master.
“--“,ifthiscontrollerisitselfmaster
(Parameter M/S Degiv.Fct.. = MASTR)
---, 1..99 --
DS-Function XXX Configuration of the defrost sequenz function (DS). For
details see chapter Defrost sequenz (DS) via CAN bus.
OFF,
MASTR,
SLAVE
OFF
DS-Group XXX Selection of which group a defrost sequenz of this
controller (1..99) belongs to.
---, 1..99 --
DS-Master XXX Selection of which controller (1..99) participating in the
defrost sequenz is the master.
“--“,ifthiscontrollerisitselfthemaster
(Parameter DS-Function = MASTR)
---, 1..99 --
DS-Wait time XXXm Wait time for the defrost sequenz 0..127 1 min