Menu 2-2-2 Zone 2
DEFROST 2 POS: XXXXX Entry Default
Counting Rate X Setpoint of time during which evaporator defrost
terminiation temperature may be within band around
0°C before defrost counter counts down
0..15 3
Defrost Counter X Setpoint of count for number of defrost cycles to be
skipped. By pressing the ↵ key the value can be set to 1
until it is automatically reset to the basic settings.
↵ 6
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 10 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 3 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 5 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1A POS: XXXXX Entry Default
Counting Rate X Setpoint of time during which evaporator defrost
terminiation temperature may be within band around
0°C before defrost counter counts down
0..15 3
Defrost Counter X Setpoint of count for number of defrost cycles to be
skipped.
By pressing the ↵ key the value can be set to 1 until it
is automatically reset to the basic settings.
6
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 10 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 3 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 5 min
Menu 2-2-4 Zone 2T Toggle
DEFROST 2A POS: XXXXX Entry Default
Counting Rate X Setpoint of time during which evaporator defrost
terminiation temperature may be within band around
0°C before defrost counter counts down
0..15 3
Defrost Counter X Setpoint of count for number of defrost cycles to be
skipped.
By pressing the ↵ key the value can be set to 1 until it
is automatically reset to the basic settings.
6
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 10 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 3 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 5 min