Menu 2-6-1 Pane Mode
Selection is made according to entry. Checkmark shows current setting.
PANE HTR POS: XXXXX Entry Default
Fixedruntime√ √
Enthalpy-ctrl rtm
Menu 2-6-2 Pane Setpoints
SETPOINTS POS: XXXXX Entry Default
Mod: xxxxxxxxxxxx Displays set frame mode (Menu 2-5-1) fixed run time
Pane On Time XX m
Pane heater on time. When making entry, make
sure that the corresponding digital input D31/D32
is set to PANE SWITCH (Menu 6-2-4)
0..120 60 min
Run Time XXX % Fixed on time, shown only when mode set to Fixed
OT (Menu 2-5-1)
--, 0..100 0 %
emerg.run time XXX % On time in loss of huimidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-1)
--, 0..100 0 %
enthalp. offs. XXX % Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-1)
-50..50 0 %
Invert Output xxx Inversion of the function of the frame heater output
(terminals 91/92)
↑,↓,
(ON/OFF)
ON