Menu 2-4-2 Zone 2
ALARM 2 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-10..30 6 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K
Menu 2-4-3 Zone 1T Toggle
ALARM 1A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-10..30 6 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K
Menu 2-4-4 Zone 2T Toggle
ALARM 2U POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High Temperature
alarm is generated
-10..30 6 °C
Low Temp Setp. XX K Temperature setpoint (difference below temperature
control setpoint) at which Low Temperature alarm is
generated
--, 0..6 4 K
Menu 2-5 Not used with this controller type.
Menu 2-6 Pane Heater
PANE HTR POS: XXXXX
1 Mode pane Move to menu 2-6-1
2 Setpoint Pane Move to menu 2-6-2