ANALOG INPUTS POS:
XXXXX
Entry Default
AIN2 Rcv. CAN xx CAN bus address of the remote case controller
which provides the locally measured analogue
value.
1..99
AIN2 Rcv. Inp x This parameter is used to specify the zone from
which the locally measured analogue value is
taken. (refers to the parameter AIN2 Rcv. Inp)
1,2
2
*Supported refrigerants: R404A, R744 (CO2), R134a, R410A, R717 (NH3), R22, R290, R407C, R507, R1270,
R402A, R502, R407F, R422A, R422D, R408A, R407D, R407A, R427A, R438A, R152a, R170, R600, R600a,
R449A, R450A, R448A, R455A, R447B, R1234ze, R1233zd, R1234yf, R513A
Praxistipusingtheexampleofthe”connectionofapressuretransmitter-1..7bar”:Here the
indication on the pressure transmitter is clear (-> -1 bar) relative to the ambient pressure The
adjustment of the pressure transmitter in the controller is carried out using absolute pressure values
(the absolute pressure cannot be negative). In order to parameterise the above pressure transmitter
with the relative pressure indication - 1 bar (at 4 mA, i.e. 0 V) at 7 bar ( at 20mA, i.e. 10 V) the ambient
pressure (1 bar) must be added. The entry is carried out as follows: 0..8 bar.