Menu 6-2-7 EEV Controller Zone 1
EEV ZONE 1 POS: XXXXX Entry Default
Pc Z 1: XX.XX Temperature control Zone 1, P-part 0..99.99
7.00
Ic Z 1: XX.XX Temperature control Zone 1, I-part
If parameter I
c
is reduced, internal learned value
(sum
of I-part) is deleted and re-learned in due course.
0..99.99
0.30
Dc Z 1: XX.XX Temperature control Zone 1, D-part 0..99.99
5.00
offs OD cab. XX % Percentage valve opening degree offset for
temperature control
If offset is changed, internal learned value (sum of I-
part) is deleted and re-learned in due course.
0..100
30 %
Psh Z 1: XX.XX Superheat control Zone 1, P-part 0..99.99
5.00
Ish Z 1: XX.XX Superheat control Zone 1, I-part
If parameter I
sh
is reduced, internal learned value
(sum
of I-part) is deleted and re-learned in due course.
0..99.99
0.10
Dsh Z 1: XX.XX Superheat control Zone 1, D-part 0..99.99
5.00
offs OD SH XX % Percentage valve opening degree offset for
superheat control
If offset is changed, internal learned value (sum of I-
part) is deleted and re-learned in due course.
0..100
10 %
emerg.c-o OD XX % Maximum valve opening degree 0..50
20 %
delay min SH XX s Delay on drop of superheat below set minimum 9..600
9 sec
setuptime XX.X m Setup time following the switching on of the
controller or following a defrost or in the event of a
blockade of the regulation.
The value entered must not be less than the current
”inject.time” parameter, otherwise the smallest valid
value will be used.
Furtherdetailsabout“Fixedvalveopeningdegreein
pumpdown/feed-inphase”seechapterFixed valve
opening degree in pumpdown/feed-in phase.
0..100.0
6.0 min
inject.time XX.X m Injection time following the switching on of the
controller or following a defrost or in the event of a
blockade of the regulation.
The value entered must not be greater than the
current ”setuptime” parameter, otherwise the largest
valid value will be used.
Furtherdetailsabout“Fixedvalveopeningdegreein
pumpdown/feed-inphase”seechapterFixed valve
opening degree in pumpdown/feed-in phase.
0..100.0
5.0 min
This menu is only visible if
the“Master”modeisactivatedinthesystemcentre,i.e.
the“Superusermode”isactivatedinthestorecomputer
For details see Operation.