EEV ZONE 1 POS: XXXXX Entry Default
OD over CAN XXX Send opening degree via CAN bus (is employed
when a demand dependent setpoint evaluation / to
shiftviaconsumer”isparameterisedinthe
corresponding pack controller)
↑,↓,(ON/OFF)
ON
15s Archiv X A few statuses and values are additionally archived
at 15 second intervals in the system centre / store
computerwhenthisparameterissetto“J”.
WARNING: This setting increases the memory
requirement and should only be activated when
needed / for diagnostic purposes.
↑,↓,(Y/N)
N
OD 3s interv XXX Select interval for output of opening degree.
OFF = 6s
ON = 3s
Control is suspended for 6 seconds when toggling.
↑,↓,
(ON/OFF)
OFF
Reset I-Sum XXX Reset I-sum (to zero) if superheat drops below set
minimumforlongerthantimesetby”delayminSH”
parameter.
OFF = I-sum not reset to zero
ON = I-sum is reset to zero
↑,↓,
(ON/OFF)
ON
edit op.deg. XXX Manual entry of valve opening degree ↑,↓,
(ON/OFF)
OFF
op.deg. Z 1 XXX % Current valve opening degree Zone 1; can be edited
when manual entry is activated
0..100 Default by
controller
Maximum OD xxx % Sets an upper limit to the opening degree output by
the case controller
20..100
100%
Lo Temp to xxK Monitoring of the t
0
transmitted by the pack
controller for unsuitably low values
NOTE: Following commissioning this value can be
set
to”-”.
10..60,–
28K
to VS corr. XXX °C Displays current corrected suction pressure
temperature on pack controller (assigned by Pack
No.)
—
—