Firmware V3.13
21.04.2021
318/466
Menu 2-2 Defrost
DEFROSTPOS: XXXXX
1 Zone 1 Move to menu 2-2-1
2 Zone 2 Move to menu 2-2-2; shown only when two-zone operation is set (Menu 6-1)
3 Zone 1T Toggle Move to menu 2-2-3; not shown when setpoint toggle is deactivated (Menu 3-3)
4 Zone 2T Toggle Move to menu 2-2-4; shown only when two-zone operation is set (Menu 6-1) and when
setpoint toggle is not deactivated (Menu 3-3)
Menu 2-2-1 Zone 1
DEFROST 1POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
2.Defrst Level XXX °C 2nd defrost stage setpoint; shown only when
single-zone operation is set (Menu 6-1)
--, -20..30
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
FordetailsseechapterMaster/slavemode–
defrost synchronisation via CAN bus.
OFF, MASTR, SLAVE OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in
the defrost via CAN bus which is the master.
"--", if this controller is itself master(Parameter M/
S Degiv.Fct.. = MASTR)
---, 1..99
DS-Function XXX Configuration of the defrost sequenz function
(DS). For details see chapter Folgeabtauung (FA)
über CAN-Bus.
OFF, MASTR, SLAVE OFF
DS-Group XXX Selection of which group a defrost sequenz of this
controller (1..99) belongs to.
---, 1..99
DS-Master XXX Selection of which controller (1..99) participating
in the defrost sequenz is the master.
"--", if this controller is itself the master(Parameter
DS-Function = MASTR)
---, 1..99
DS-Wait time XXXm Wait time for the defrost sequenz 0..127 1 min