Menu 2-2-2 Zone 2
DEFROST 2POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-2-3 Zone 1T Toggle
DEFROST 1APOS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
2.Defrst Level XXX °C 2nd defrost stage setpoint; shown only when
single-zone operation is set (Menu 6-1)
--, -20..30 –
Menu 2-2-4 Zone 2T Toggle
DEFROST 2APOS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 5 °C
Wait Time XX m Waiting time setpoint between cooling and
defrost
0..15 0 min
Drip Time X m Waiting time (drip time) setpoint between defrost
and cooling
0..15 0 min
Menu 2-3 Fan
FANSPOS: XXXXX
1 Zone 1 Move to menu 2-3-1
2 Zone 2 Move to menu 2-3-2; shown only when two-zone operation is set (Menu 6-1)
3 Zone 1T Toggle Move to menu 2-3-3; not shown when setpoint toggle is deactivated (Menu 3-3)
4 Zone 2T Toggle Move to menu 2-3-4; shown only when two-zone operation is set (Menu 6-1) and when
setpoint toggle is not deactivated (Menu 3-3)