Firmware V3.13
21.04.2021
321/466
Menu 2-4-1 Zone 1
ALARM 1POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Tempeature alarm is generated
0..30 10 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K
Menu 2-4-2 Zone 2
ALARM 2POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Tempeature alarm is generated
0..30 10 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K
Menu 2-4-3 Zone 1T Toggle
ALARM 1APOS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Tempeature alarm is generated
0..30 8 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K
Menu 2-4-4 Zone 2T Toggle
ALARM 2APOS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Tempeature alarm is generated
0..30 8 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 2 K