Firmware V3.13
21.04.2021
353/466
Menu 1-4 Fan Zone1
FANS 1 XXXXX
Fans XXX Displays current fan status
Temp. R1.1 XXX °C Displays current evaporator defrost termination temperature Input Z31/Z32
Fans Delay XXX °C displays fan start temperature setpoint
Menu 1-5 Alarm
ALARM XXXXX
Alarm Relay XXX Displays current OFF/ON status of alarm output Terminal 15/16/18
Hi Temp Setp.1 XX °C Displays high temperature setpoint Zone 1
Lo Temp Setp.1 XX K Displays low temperature setpoint Zone 1
Hi Temp Setp.2 XX °C Displays high temperature setpoint Zone 2; shown only when two-zone operation
is set (Menu 6-1)
Lo Temp Setp.2 XX K Displays low temperature setpoint Zone 2; shown only when two-zone operation is
set (Menu 6-1)
Coldroom Door 1 XXX Displays current OFF/ON status of coldroom door input Terminal D31/D32
Coldroom Door 2 XXX Displays current OFF/ON status of coldroom door input Terminal D21/D22
Menu 1-6 Frame Heater
MODE XXXXX
Frame Heater XXX Displays current OFF/ON status of frame heater output Terminal 91/92/93
Run Time XXX % Displays current frame heater on time
Humidity XXX % Displays current room air humidity (transmitted via CAN bus from VS pack controller
with fitted humidity sensor)
Room temp. XX °C Displays current room air temperature (transmitted via CAN bus from VS pack controller
with fitted room air temperature sensor)