Menu 6-5 Alarm priorities
ALARMPRIOS POS: XXXXX Entry Default
Prio.Refrig. Pt. X Global setting of alarm priority via refrigaration point
priority (Menu 6-1) (Y)
↑,↓,
(Y/N)
N
Priority: XX Displays refrigeration point priority (Menu 6-1); only
shown when refrigeration point priority is set to Y
Following parameters are only shown when refrigeration point priority is set to N. Meaning of valid entries for alarm priority is as follows:
- = Event ignored
0 = Message (enterd only in message log)
1 = Priority 1 alarm
..
99 = Priority 99 alarm
Low Temp. Temperature below low alarm limit.
Priority applies to alarms Low Temp. Zone 1, Low
Temp. Zone 2
-, 0..99 2
High Temp. Temperature above high alarm limit.
Priority applies to alarms High Temp. Zone 1, High
Temp. Zone 2
-, 0..99 1
Sensor Fault Temperature sensor failure -, 0..99 2
Door Open Coldroom door open longer than time delay; pririty
applies to Coldroom Door Open alarm
-, 0..99 1
No Defrost No defrost within alarm delay time. Priority applies to No
Defrost alarm
-, 0..99 0
Timer-Term. Defrost Defrosting terminated by safe defrost time -, 0..99 0
Power Failure Start following power failure -, 0..99 0
First Start Controller Startup (basic settings are loaded!) -, 0..99 2
Manual Shutoff Manual switch Input D31/D32 set OFF -, 0..99 0
Hardware Fault Internal hardware defect. Priority applies to alarms
EEPROM Defective, RTC Defective, Flash Memory
Defective
-, 0..99 1
Setpoint Change Message generated when changing setpoints 0..99 0
Refrig.Pt.Dis. Cooling interrupted by VS pack controller via CAN bus -, 0..99 0
Battery Voltage Battery low -, 0..99 0
Check t0 The pack controller to is not received via CAN bus;
priority is given to the messages Check to Z1, Check to
Z2 (see also chapter Low Temperature Monitoring t0)
-, 0..99 2
Sensor Fault eev EEV Control sensor failure. Priority applies to alarms
Sensor Break EEV Z1, Sensor Break EEV Z2
-, 0..99 2
eev ctrl block EEV control stalled. Priority applies to alarms EEV Stall
Detect Z1, EEV Stall Detect Z2
-, 0..99 0