ALARMPRIOS POS: XXXXX Entry Default
wrong ctrlr type Configuration error: Invalid controller type set on DIP
Switch S3. Priority applies to Wrong Controller Type
alarm
-, 0..99 0
emerg.cut-out SH Superheat drop below minimum level for duration of
delay time
-, 0..99 --
OD manual Valve opening degree defined by manual entry. Priority
applies to alarms VO Manual Zone 1, VO Manual Zone
2
-, 0..99 0
config:M/S w HG Configuration error: Simultaneous setting of parameters
for master-slave mode and discharge gas defrosting
-, 0..99 2
Check OD Alarm due to implausible opening degree
(see chapter Implausible opening position alarm)
-, 0..99 0
Extern.Alarm Alarm for registering external alarms, default text is
“CO2-Alarm”
-, 0..99 0
Menu 6-6 Em.Powersupply (Emergency Power supply)
EM.POW.SUP POS: XXXXX Entry Default
Cool.funct.OFF xxx Functionality of the cooling switched off during
emergency power supply? (Y/N)
↑,↓,(Y/N) N
Defr.funct.OFF xxx Functionality of the defrosting switched off during
emergency power supply? (Y/N)
↑,↓,(Y/N) N
Fan funct. OFF xxx Functionality of the fan switched off during
emergency power supply? (Y/N)
↑,↓,(Y/N) N
Frame fct.OFF xxx Without function ↑,↓,(Y/N) N
Light fct. OFF xxx Functionality of the light during emergency power
supply? (Y/N)
↑,↓,(Y/N) N