Parametrisation of the enhanced fan control
The relevant parameters for the enhanced fan control are in the Operation menu of the case controller under
menu 2 Setpoints - 6 Fans - Zone 1+2 and can be used for the normal setpoint. The desired operating mode
mustfirstbeselectedforthefancontrol.ThisisdoneviatheparameterBetrArt.
The following four parameters are available for the operating mode:
DAUERLAUF(continuousoperation)
VORLAUF(flow)
NACHLAUF(overrun)
VERZ.N.ABT.(delay after defrost)
ThetwoparametersLüfteranlaufandLüfter Über are used for control of the fans via the temperature at the
evaporator sensors R1.1 and R1.2.. These parameters are not effective in all operating modes.