Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-222 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET REPORT
Description: Allows changing of the system alarm reporting function.
Command Level: 6
Syntax: SET REPORT
SE RE
Comments: The current status of the system reporting function as it is configured is first
displayed, and then the user can change the configuration, if desired. Parameters
displayed include System Alarm Report mode, which enables the reporting and allows
the user to choose between single (system alarm reporting is considered successful if the
system connects with a modem or sends an Email), or continuous (system alarm
reporting is considered successful when the user issues an ACK command), or off. The
User Calling Sequence allows the programming of users in the order in which the system
will call in an attempt to communicate an alarm indication. The Retry Time is the time
interval between the calling or Emailing of the last person designated in the user
sequence and the recalling or Emailing of the first user in the sequence. The Auto-logoff
Time is the interval the system waits with a pending report before issuing a priority
message, and logging the user off.
In the typical screen display below, the system will first attempt to report system alarms to
user No. 6. If not successful, it will attempt to call user No. 5, followed by user No. 4,
then user No. 1. The system will try to call or Email user No. 6 again after 10 minutes
and continue the sequence until the system gets through to any of the four users. After it
gets through to one of the users, the system will no longer attempt to contact the other
three users (single), or until the user issues an ACK command (continuous).
If the ACK (acknowledge) command is entered by any user to acknowledge new system
alarms which have not been reported, no system alarm report attempts will be made for
that particular alarm.
Notes: A maximum of 20 numbers can be entered in the User Calling Sequence. For
Email alarm notification, also use the SET EMAIL command.
Related Commands: REPORT, SET EMAIL
Example:
Command<6>: SET REPORT
System Alarm Report mode: Single
User Calling Sequence: 6 5 4 1
Retry Time: 10m
Auto-logoff Time: 60sec
System Alarm Report mode: Continuous
User Calling Sequence: 6 5 4 1
Retry Time: 10m
Auto-logoff Time: 60sec