User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-223
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET RLY
Description: Allows manual energizing of each of the control relays.
Command Level: 6, or level 5 if the relay channel being operated is configured in the
user’s channel group.
Syntax: SET RLY [[node_number]channel_number]
SE RL [[node_number]channel_number]
Comments: The SET RLY command could generate an alarm log entry if the relay is
configured as an alarm type. Additionally, if configured as an alarm type, this alarm could
initiate a phone report or Email message.
A jumper is provided on the relay circuit card which can be used to disable the SET RLY
and CLR RLY commands.
If a level 5 user attempts to set a relay channel not configured in the user’s channel
group, the following message is issued. "Illegal request, not configured to access this
channel" or when using the voice feature "Relay access refused".
Notes: Any user using the SET RLY command will have his name and this action
recorded in the event log. The relay can be released using the command CLR RLY.
Related Commands: CLR RLY
Example:
Command<6>: SET RLY
Set Relay: 0005
Set Relay: