EasyManua.ls Logo

Endress+Hauser Proline Promass E 500 - 10.6.13 Configuring the Low Flow Cut off

Endress+Hauser Proline Promass E 500
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning Proline Promass E 500 PROFIBUS PA
136 Endress+Hauser
10.6.13 Configuring the low flow cut off
The Low flow cut off wizard systematically guides the user through all the parameters
that must be set to configure low flow cut off.
Navigation
"Setup" menu → Low flow cut off
Low flow cut off
Assign process variable
→  136
On value low flow cutoff
→  136
Off value low flow cutoff
→  136
Pressure shock suppression
→  136
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign process variable Select process variable for low
flow cut off.
Off
Mass flow
Volume flow
Corrected volume
flow
*
On value low flow cutoff A process variable is selected
in the Assign process variable
parameter (→  136).
Enter on value for low flow cut
off.
Positive floating-
point number
Depends on country
and nominal
diameter
Off value low flow cutoff A process variable is selected
in the Assign process variable
parameter (→  136).
Enter off value for low flow cut
off.
0 to 100.0 %
Pressure shock suppression A process variable is selected
in the Assign process variable
parameter (→  136).
Enter time frame for signal
suppression (= active pressure
shock suppression).
0 to 100 s
* Visibility depends on order options or device settings

Table of Contents

Related product manuals