Proline Promass E 500 PROFIBUS PA Technical data
Endress+Hauser 271
Low flow cut off The switch points for low flow cut off are user-selectable.
Galvanic isolation The outputs are galvanically isolated:
• from the power supply
• from one another
• from the potential equalization (PE) terminal
protocol-specific data
Manufacturer ID 0x11
Ident number 0x156D
Profile version 3.02
Device description files (GSD,
DTM, DD)
Information and files under:
• https://www.endress.com/download
On the device product page: PRODUCTS → Product Finder → Links
• https://www.profibus.com
Supported functions • Identification & Maintenance
Simplest device identification on the part of the control system and
nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Configuration of the device
address
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e.g. FieldCare)
Compatibility with
earlier model
If the device is replaced, the measuring device Promass 500 supports the
compatibility of the cyclic data with previous models. It is not necessary to
adjust the engineering parameters of the PROFIBUS network with the
Promass 500 GSD file.
Earlier models:
• Promass 80 PROFIBUS PA
• ID No.: 1528 (hex)
• Extended GSD file: EH3x1528.gsd
• Standard GSD file: EH3_1528.gsd
• Promass 83 PROFIBUS PA
• ID No.: 152A (hex)
• Extended GSD file: EH3x152A.gsd
• Standard GSD file: EH3_152A.gsd
System integration Information regarding system integration → 97.
• Cyclic data transmission
• Block model
• Description of the modules
16.5 Power supply
Terminal assignment → 40
Available device plugs → 40
Available device plugs → 41