Proline Promass E 500 PROFIBUS PA Technical data
Endress+Hauser 277
Example of maximum measurement error
E [%]
Q [%]
0 5 10 15 20 25 30 35 40 45 50 60 6555
0
0.5
1.0
1.5
2.0
2.5
70 75 80 85 90 95 100
A0030289
E Maximum measurement error in % o.r. (example)
Q Flow rate in % of maximum full scale value
16.7 Mounting
Mounting requirements → 22
16.8 Environment
Ambient temperature
range
→ 25
Temperature tables
Observe the interdependencies between the permitted ambient and fluid
temperatures when operating the device in hazardous areas.
For detailed information on the temperature tables, see the separate document
entitled "Safety Instructions" (XA) for the device.
Storage temperature
Climate class DIN EN 60068-2-38 (test Z/AD)
Relative humidity The device is suitable for use outdoors and indoors with a relative humidity of 4 to 95 %.
Operating height According to EN 61010-1
• ≤ 2 000 m (6 562 ft)
• > 2 000 m (6 562 ft) with additional overvoltage protection (e.g. Endress+Hauser HAW
Series)
Degree of protection Transmitter
• IP66/67, Type 4X enclosure, suitable for pollution degree 4
• When the housing is open: IP20, Type 1 enclosure, suitable for pollution degree 2
• Display module: IP20, Type 1 enclosure, suitable for pollution degree 2
Sensor
• IP66/67, Type 4X enclosure, suitable for pollution degree 4
• When the housing is open: IP20, Type 1 enclosure, suitable for pollution degree 2