FT-111, User Manual Rev. 2.0.0, June 2022 Page 109 of 137
11.11.2 Data Format
Data format of weight value can be programmable for Floating point (IEEE 754) or Integer. Refer to
parameter [ 191 ].
11.11.3 EtherNet/IP Parameters
EtherNet/IP parameters can be adjusted by keys in programming mode. Refer to parameter block [ 19- ].
Additionally, EtherNet/IP parameters set up are done by EtherX PC software over Local Network Area or by
IndFace2x. Both softwares on www.flintec.com
11.11.4 EDS Configuration
EtherNet/IP data structures consist of 2 pcs Input-2 words and 2 pcs Output-2 words. EDS configuration for
PLC programmers is shown in Figure 11.17 and Figure 11.18.
Figure 11.17 Configuration of module properties without EDS file