4.2 Temperature Controller/Servo/Inverter Connection 4-13
4.2.8 DMC10
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Controller
Rotary switch for device address
CPL communication setting
Make the following settings on the PC loader. (Underlined setting: default)
Available Device Memory
The available setting range of device memory varies depending on the controller model. Be sure to set within the range
available for the controller to be used. Use [TYPE] when assigning indirect device memory for macro programs.
* The number of times EEPROM can be reprogrammed is limited (approx. 100,000 times). Accordingly, we recommend that
you write such a parameter as to be reprogrammed frequently into RAM, where the number of reprogramming times is
not limited. However, when the parameter has been written into RAM, and the power is turned off and back on again,
data in EEPROM is transferred.
For more information, refer to the instruction manual for the controller issued by the manufacturer.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 / Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-232C
/ RS-422/485
Baud Rate 4800 / 9600 / 19200
bps
Data Length 7 / 8
bits
Stop Bit 1
/ 2 bits
Parity None / Odd / Even
Targe t Por t N o. 1 to 31
MODULE ADDRESS Setting Remarks
1 to F Communication is disabled when “0” is set.
Setting Items Setting Remarks
CPL/MODBUS 0: CPL
See “20. MODBUS”.
Baud rate
1: 4800 bps
2: 9600 bps
3: 19200 bps
Data type
0: 8 bits / 1 bit / even
1: 8 bits / 2 bits / none
4
3
2
1
0
F
E
D
C
B
A
9
8
7
6
5
Device Memory TYPE Remarks
--- 00H
Without “*”: RAM
With “*”: RAM + EEPROM