16.2 Temperature Controller/Servo/Inverter Connection 16-25
16.2.1 PYX (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Temperature Controller
The communication parameter can be set using keys attached to the front of the temperature controller.
Be sure to match the settings to those made under [Communication Setting] of the editor.
(Underlined setting: default)
* The communication function of the temperature controller can be selected from Fuji protocol or Modbus protocol at the time of purchase.
For communication with a V9, select a model on which the Modbus protocol is available.
* The following communication parameters are fixed; baud rate: 9600 bps, data length: 8 bits, stop bit: 1 bit, and parity: odd.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1:1 / 1:n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1:n Multi-link2 (Ethernet)
Signal Level RS-422/485
Do not change the default settings because these settings on the
temperature controller cannot be changed.
Baud Rate 9600 bps
Data Length 8 bits
Stop Bit 1 bit
Parity Odd
Target Port No. 1 to 31
Parameter Item Setting Example
Digital transmission function
(station number)
1
to 31 1
Device Memory TYPE Remarks
000H
101HRead only
402H
303HRead only