16-90 16. Fuji Electric
16.2.32WE1MA (Ver. B) (MODBUS RTU)
Communication Setting
Editor
Communication setting
(Underlined setting: default)
Electronic Multimeter
Communication parameters can be set by operating the front-mounted keys of the electronic multimeter.
Be sure to match the settings to those made under [Communication Setting] of the editor.
(Underlined setting: default)
* The communication parameter (data length) is fixed to 8 bits.
Available Device Memory
The available setting range of device memory varies depending on the model. Be sure to set within the range available for the
model to be used. Use [TYPE] when assigning indirect device memory for macro programs.
Item Setting Remarks
Connection Mode
1 : 1 / 1 : n
/ Multi-link2 /
Multi-link2 (Ethernet) /
1 : n Multi-link2 (Ethernet)
Signal Level RS-422/485
Baud Rate 4800 / 9600
/ 19200 / 38400 bps
Data Length 8 bits
Stop Bit 1
/ 2 bits
Parity None / Even
/ Odd
Target Port No. 0 to 247 0: Broadcast
Setting
Component
Setting No. Item Setting Example
Adr 231C Address 1
to 247 1
bPS 232C Baud rate 4800 / 9600
/ 19200 / 38400 bps 9600
PAr 233C Parity
E: Even
o: Odd
-: None
E
StoP 234C Stop bit 1
/ 2 bits 1
WEr 235C Protocol version B: Version B B
Device Memory TYPE Remarks
4 (holding register) 02H
3 (input register) 03H Read only