1.3 Connection Methods 1-33
MONITOUCH Setting
Local port setting (Local mode)
When [Set Local Port No. in Main Menu] is checked in the [Multi-link] window, the local port number must be set in Local
mode on the V9 series.
1. Transfer the screen program.
2. Switch to Local mode on MONITOUCH.
3. Press the [Communication Setting] switch and display the Communication Setting screen.
4. Set the [Local Port No] on the [Individual Parameter] tab window.
5. Press the [Apply] switch.
Wiring
When Connected at CN1
This shows the situation when a multi-link connection is made at CN1. It is convenient to use the Hakko Electronics’ optional
terminal converter “TC-D9”.
When a TC-D9 is used:
Set the slide switch of “TC-D9” to ON (2-wire system).
When no TC-D9 is used:
Install jumpers between +SD and +RD as well as SD and RD.
FG
+RD
−RD
+SD
−SD
SG SG
TC-D9
FG
+RD
−RD
+SD
−SD
SG
TC-D9
FG
Name
NameName
+RD
−RD
+SD
−SD
SG
TC-D9
Terminating resistance
(OFF)
Shielded
Shielded
Shielded
To the RS422 port of
the connected device
Receive data (+)
Receive data ()
Send data (+)
Send data ()
Terminating resistance
(ON)
Terminating resistance
(OFF)
Terminating resistance
(ON)
* Jumpers may not be necessary,
depending on the connected device.
* Use shielded twist-pair cables.
Terminating resistance
(OFF)
Shielded
Shielded
Shielded
Terminating resistance
(ON)
Terminating resistance
(OFF)
Terminating resistance
(ON)
To the RS422 port of
the connected device
Receive data (+)
Receive data ()
Send data (+)
Send data ()
* Jumpers may not be necessary,
depending on the connected device.
* Use shielded twist-pair cables.