CHAPTER
9
SPECIAL CONDITION OF USE AND
APPROVED STANDARDS
Approval Rating
Certification Approval Rating
FM Nonincendive for use in Class I, Division 2, Groups A, B, C & D
Class I, Zone 2, IIC T*
CSA Class I, Division 2, Groups A, B, C & D T*
ATEX II 3 G Ex nA IIC T* Gc
Temperature class
(T*):
Module
T3C 900G03
T5 900G32
T4 900H03, 900P01, 900P24, 900RR0, 900CP1, 900SP1, 900U01
T6 900A01, 900H32, 900PSM, 900R04, 900R08, 900R12,
900R08R, 900R12R
Table 9-1: Approval Rating
Special Condition of Use for Division 2/Zone
2 Hazardous Location Installation
For the United States
n The installer shall provide transient over-voltage protection
external to the apparatus such that the voltage at the supply
terminal of the apparatus does not exceed 140% of the voltage
rating of the equipment.
n The equipment shall be mounted in an enclosure providing a
minimum degree of protection of IP54 in accordance with
ANSI/IEC 60529., and in a tool-secured enclosure which meets
the requirements of ANSI/ISA 60079-0 and ANSI/ISA 60079-15.
179