93
n Current Rating:
l 4 A at 240 VAC or 30 VDC resistive load;
l 0.5 A at 240 VAC or 30 VDC incandescent lamp load
n OFF to ON response time: 11 ms Max
n ON to OFF response time: 8 ms Max
n Maximum Leakage Current: 1 mA @ 350 VDC
n Power Supply Loading: 5V- 110mA maximum; 24V-100mA
maximum
n Galvanic Isolation:
l Relay output contact to relay output contact
l Relay output contact to logic
Pulse Input/Frequency Input Module (4 Channels)
The 4 Channel Pulse/Frequency/Quadrature Module provides four
different functionalities in the form of Pulse Input, Frequency
measurement, Quadrature encoder input and Pulse Output. Each of
the 4 channels can be configured for any one of these four
functionalities; with the exception that quadrature encoder input (A
and B pulses) can be applied to only Channels 1 and 2 respectively.
When configured for quadrature, Channels 3 and 4 will still be
available for use.
The Pulse Output functionality uses the digital output available on the
module for outputting pulses. 4 Digital Outputs, Open collector, 5 to
24 V DC, 30 mA max used for fast signaling.
Pulse Input Type supports:
n Input Voltage: 0 V DC to 24 V DC
n ON Voltage Level: 3.0 V DC minimum
n OFF Voltage Level: 1.0 V DC maximum
n Input Impedance: 25K ohm
n Frequency: 10 KHz maximum
n Minimum Pulse Width: 3 μsec
n Pulse Counter: 32 bits
n Digital Output:
l If preset action ON, output turns ON for 1 second.
l If preset action OFF, output latches ON, and remains ON until
counter reset command.
Pulse Output supports: