n OFF to ON Response Time: 4 ms maximum with 1.5 lines cycle
maximum
n ON to OFF Response Time: 4 ms maximum with 2 lines cycle
maximum
n Power Supply Loading: 5 V: 130 mA max and 24 V: 0 mA
n RTP support. For more information, see Using an RTP to field
wiring the 16 Point AC DI section.
Digital Input Module (32 channels) - DC Voltage Type
The Digital Input Module-DC Voltage Type is sinking type module with
below features:
n Channel Density: 32 Channels with two groups of input, each with
a pair of terminals of connection to common
n Input voltage range: 10 V DC to 32 V DC.
n Isolation: Galvanic ally isolated in 2 groups of 16 points to rack (30
V DC maximum)
n ON Voltage Level: 9.5 V DC minimum
n OFF Voltage Level: 3.5 V DC maximum
n Minimum ON Current: 1.0 mA
n Maximum OFF Current: 0.7 mA
n OFF to ON Response Time: 5 ms maximum
n ON to OFF Response Time: 5 ms maximum
n Power Supply Loading: 5 V: 215 mA maximum and 24 V: 0 mA
n 20 pin EURO style terminal block
n RTP support, 2 RTP are needed for each module. For more
information, see Using Dual RTPs to field wiring the 32 Point DC
DI section.
Relay Output Module (8 Channels)
8 channel electromechanical relay output supports:
n Channel 1, Channel 2, Channel 7 and Channel 8 are form C type,
provide both NO and NC contact
n Channel 3 ~ Channel 6 are form A type, provide NO contact.
n Input Voltage: 120/240 V AC or 30 VDC
n Output Device: Electromechanical relay; Specified relay life:
1000000 cycles