I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams
90 HC900 Process Controller Installation and User Guide Revision 19
06/14
OUT 1+
OUT 1 -
OUT 2+
OUT 2 -
OUT 3+
OUT 3 -
OUT 4+
OUT 4 -
+
-
OUT 1+
OUT 1 -
OUT 2+
OUT 2 -
OUT 3+
OUT 3 -
OUT 4+
OUT 4 -
Figure 464 channel Analog Output Wiring Diagram
8 and 16 channel Analog Output Module Wiring
Examples of high level Analog Output Module wiring are shown in Figure 47 and Figure 48.
Specifications for this module and for other modules are given in the Specifications section of this manual.
Before installing, be sure to determine power requirements. See page 38 and 77.
Isolation
The outputs are grouped with 4 outputs per group (outputs 1-4, 5-8, 9-12, 13-16). Groups are isolated from
each other; outputs are non-isolated within each group.
Shield Grounding
Shields must be grounded as described under Shield Grounding at the beginning of this section.
Hazardous voltages exist at terminal blocks.
Using switches at field devices disconnect the field wiring form power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.