Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
Revision 19 HC900 Process Controller Installation and User Guide 219
06/14
Analog Input/Digital Input/Digital Output/Analog Output
A single DI/DO/AO-RTP and cable is used with the following modules: See page
• 4-point Analog Output 219
• 16-point Contact Digital Input 221
• 16-point DC Digital Input 222
• 16-point AC Digital Input 224
• 16-point DC Digital Output 225
• 8-point AC Digital Output 228
• 8-point Analog Output 231
Dual DI/DO/AO-RTPs and cables are used with the following modules: See page
• 16-point Analog Output 234
• 16-point Analog Input 235
• 32-Point DC Digital Output 238
• 32-Point DC Digital Input 240
4 Point Analog Output
Step Action
1 ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 92).
• Remove appropriate key tabs from terminal block to allow mating with the module. See page 75.
• Connect desired cable to AO module at controller. Choose from:
900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long
900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long
900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long
• Install AO module label onto the module connector cover.
• Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 70).
2 Mount RTP to DIN rail.
• Latch to rail. See page 244.
• Connect cable to RTP