Specifications - General Specifications
194 HC900 Process Controller Installation and User Guide Revision 19
06/14
Specifications
General Specifications
C30 C50 C70 C75
Controller Design
Modular design with metal rack enclosure, power supply, controller CPU and user selectable
I/O module types.
Rack Mounting and
Installation
Surface mounting with 4 screws in back of rack.
Installation Category II, Pollution Degree 2, IEC 664, UL840 Installation coordination
Controller I/O
support
4, 8, or 12 I/O slots per Rack
None (requires
remote I/O racks)
Remote I/O racks
None
1 w/o switch, using Ethernet direct cable. Up
to 4 with recommended Honeywell switches
(part no. 50008930-001).
1 w/o switch, using
Ethernet direct cable. Up
to 5 with recommended
Honeywell switches (part
no. 50008930-001)
Remote I/O interface
type
None
Separate Ethernet 100Base-T port on CPU, RJ-45 connection,
dedicated communications link
Remote I/O Distance
None
100 m (328 ft.) Ethernet cable, controller to remote rack or controller
to switch. Up to two switches per connection, 300m (984 ft.), and
maximum distance.
750m (2460 ft.) Fiber optic cable, controller to remote rack or
controller to switch. Up to two switches per connection, 1500m
(4920 ft) maximum distance.
Fiber Optics Equipment Recommendations
Ethernet Switch Moxa Unmanaged Ethernet Switch model
EDS-308-MM-SC with (6) 10/100 Ethernet
ports, (2) multi-mode fiber ports with SC
Connectors (require 24VDC power)
Converter Moxa Media Converter model IMC-101-M-
SC with (1) 10/100BaseT(X) to 100BaseFX
multi-mode fiber port with SC connectors
(require 24VDC power)
Fiber Cable Multi-mode, Duplex, 62.5/125 with SC
connectors on both ends
Copper Ethernet Cable Shielded Cat5 Ethernet cable
I/O Capacity
Combined Analog and
Digital
384
1920
Analog Inputs
192
960
Analog Outputs
40
48 with heat de-
rating
192 with external
power source
200
240 with heat de-rating
960 with external power source
Rack Size
4 I/O slot chassis
5.4”(137mm) H” x 10.5”(266.7mm) W x 6.0”
*
(151.7 mm) D (rear mounting plate extends
height to 6.9” (175.3mm)
8 I/O slot chassis
5.4”(137mm) H x 16.5”(419.1mm) W x 6.0”
*
(151.7mm) D (rear mounting plate extends height
to 6.9” (175.3mm)
8 I/O slot chassis with
redundant power
support
5.4”(137mm) H x 20.9”(530.9.1mm) W x 6.0”
*
(151.7mm) D (rear mounting plate extends
height to 6.9” (175.3mm)
12 I/O slot chassis
5.4”(137mm) H x 22.5”(571.5mm) W x 6.0”
*
(151.7mm) D (rear mounting plate extends height
to 6.9” (175.3mm)

Table of Contents