Redundant Operating Characteristics - Failover
158 HC900 Process Controller Installation and User Guide Revision 19
06/14
Figure 84Lead/Controller synchronization
Failover
Automatic Failover
Triggered on any of the following conditions of the Lead Controller:
Loss of communications with I/O Rack(s)
Processor exception conditions
Error conditions that occur in the following areas will not cause a failover:
Loss of communications to a Host on a network
Loss of communications to Modbus Slave devices
Loss of communications to Operator Interface
Loss of communications with a Peer controller
During the transition from the Lead to the Reserve, analog and digital output status is maintained at the
I/O racks.