Appendix - Installation of Remote Termination Panels (RTPs) - Analog Input/Digital Input/Digital Output/Analog
Output
230 HC900 Process Controller Installation and User Guide Revision 19
06/14
RTP Cable wire positions and colors (Applies to 4 AO, 16 DI, 16 DO, 8 DO)
Twisted Pair Number HC900 Module TB Position RTP J1 Plug Connector Color
1 1 6 Black
2 7 Red
2 4 9 Black
5 10 White
3 6 20 Black
7 19 Green
4 9 17 Black
10 16 Blue
5 11 15 Black
12 14 Yellow
6 14 12 Black
15 11 Brown
7 16 1 Black
17 2 Orange
8 19 4 Red
20 5 White
9 3 8 Red
8 18 Green
10 13 13 Red
18 3 Blue
RTP Internal schematic (Applies to 4 AO, 16 DI, 16 DO, 8 DO)