Grounding requirementsGrounding requirements
This equipment must be grounded properly for proper operation and safety. In the United States, you must install the equipment in
accordance with NFPA 70, 1999 Edition (National Electric Code), Article 250, as well as any local and regional building codes.
In Canada, you must install the equipment in accordance with Canadian Standards Association, CSA C22.1, Canadian Electrical Code.
In all other countries, you must install the equipment in accordance with any regional or national electrical wiring codes, such as the
International Electrotechnical Commission (IEC) Code 364, parts 1 through 7. Furthermore, you must be sure that all power distribution
devices used in the installation, such as branch wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with this equipment, Hewlett Packard Enterprise recommends the use of a PDU
that is either permanently wired to the building’s branch circuit or includes a nondetachable cord that is wired to an industrial-style plug.
NEMA locking-style plugs or those complying with IEC 60309 are considered suitable for this purpose. Using common power outlet strips
to supply power to this equipment is not recommended.
Grounding requirements 17

Table of Contents

Other manuals for HP HPE Synergy 12000 Frame

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP HPE Synergy 12000 Frame and is the answer not in the manual?

HP HPE Synergy 12000 Frame Specifications

General IconGeneral
Form FactorRack-mountable
Maximum Compute Modules12
Management ModuleHPE Synergy Composer
CoolingRedundant fan modules
Power SupplyRedundant power supplies
NetworkingHPE Synergy 12000 Frame Interconnect
Product TypeBlade Enclosure
Width44.5 cm
ComplianceFCC, VCCI, BSMI, CCC, KCC, RoHS
Depth36.25 in (92.08 cm)

Related product manuals