EasyManua.ls Logo

IDEC MICRO/I HG1P-ST32 Series - Page 1517

IDEC MICRO/I HG1P-ST32 Series
1665 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WindO/I-NV4 Users Manual 31-31
2 USB Autorun Function
31
External Memory Devices
dst_plc_port
Specify the port number of the download destination PLC.
Example: dst_plc_port = 2101
command = LDR_UPLOAD
dst_path (required)
Specify the path to the folder (250 or less characters) where the uploaded PLC program will be saved.
Use “A:\” for an SD memory card and “B:\” for a USB flash drive.
src_port (required)
Specify the name of the MICRO/I port to which the PLC to upload from is connected. For details about the port name,
refer to Chapter 4 “Interface Configuration” on page 4-35.
src_net_no (required when specifying the destination as a slave number or External Device ID)
If the communication interface that connects the PLC for uploading is the serial interface, specify the slave number. If
the communication interface is the Ethernet interface, specify the External Device ID. Specify the same number set as
the slave number or External Device ID for the PLC.
src_plc_ip (required when specifying the destination as an IP address)
Specify the IP address of the upload source PLC.
Example: src_plc_ip = 192.168.0.1
src_plc_port
Specify the port number of the upload source PLC.
Example: src_plc_port = 2101
When specifying the destination as an IP address and this item is left blank or contains an illegal value, the
MICRO/I assumes that the value is "2101". This item is not required when specifying the destination as a
slave number or External Device ID.
COM1: The name of the serial interface varies based on the model.
HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F: COM1
HG2G-5T: SERIAL1(RS232C)
HG1G: COM(RS232C)
COM2: The name of the serial interface varies based on the model.
HG5G/4G/3G/2G-V: COM2(RS232C) or COM2(RS422/485)
HG4G/3G, HG2G-5F: COM2
HG2G-5T: SERIAL1(RS422/485)
HG1G/1P: COM(RS422/485)
ETHER: Ethernet interface (LAN)
When specifying the destination as an IP address and this item is left blank or contains an illegal value, the
MICRO/I assumes that the value is "2101". This item is not required when specifying the destination as a
slave number or External Device ID.

Table of Contents

Related product manuals