Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F9-47 63791
Fault protection action
selection 0
Ones: Overcurrent during acceleration/
deceleration/operation at constant
speed (E2/E3/E4)
0: Coast to stop
2: Restart upon fault
Tens: Overvoltage during acceleration/
deceleration or at constant speed (E5/
E6/E7)
0: Coast to stop
2: Restart upon fault
Hundreds: Reserved
5: Disabled
Thousands: Undervoltage (E9)
0: Coast to stop
2: Restart upon fault
Ten thousands: AC drive overload
(E10)
0: Coast to stop
2: Restart upon fault
500 -
At stop
F9-47
on page
303
F9-48 63792
Fault protection action
selection 1
Ones: Motor overload (E11)
0: Coast to stop
1: Decelerate to stop
2: Restart upon fault
4: Warning
5: Disabled
Tens: Reserved
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
Hundreds: Output phase loss (E13)
0: Coast to stop
1: Decelerate to stop
2: Reset upon fault
4: Warning
5: Disabled
Thousands: IGBT overtemperature
(E14)
0: Coast to stop
Ten thousands: External device fault
(E15)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Disabled
10050 -
At stop
F9-48
on page
303
List of Drive Unit Parameters
-171-